In short: number of sections = the room's heat loss ÷ the output of one section at your system's real temperature. An averagely insulated room needs ≈100 W per m²; a 500 mm aluminium section gives about 170–190 W at the catalogue rating (ΔT 50). So a 15 m² room needs ≈8–9 sections. If the boiler or heat pump runs at low temperature, the same section gives almost half as much and the radiator must be larger.
This article is part of the heating systems guide.
The formula
Number of sections = room heat loss (W) ÷ output of one section (W) at the real temperature
Round the result up. The same rule applies to panel radiators: you match the room's heat loss to a panel size (height × length × type) from the manufacturer's table.
Quick table by room size
500 mm aluminium section, ≈180 W (ΔT 50), averagely insulated room (≈100 W/m²), 2.7 m ceiling:
| Room | Output needed | Sections (ΔT 50) | Sections (55/45 °C system) |
|---|---|---|---|
| 10 m² | ≈1.0 kW | 6 | 11 |
| 15 m² | ≈1.5 kW | 9 | 17 |
| 20 m² | ≈2.0 kW | 12 | 22 |
| 25 m² | ≈2.5 kW | 14 | 27 |
When one radiator needs more than 12–14 sections, it is better to split it into two (for example under two windows) or choose a more powerful panel radiator.
What does ΔT 50 mean and why does it matter?
Catalogue radiator outputs are measured under the European standard EN 442, usually at 75/65/20 °C: water enters at 75 °C, leaves at 65 °C, and the room is 20 °C. The difference between the mean water temperature and the room is 50 °C (ΔT 50). At lower temperatures a radiator gives much less heat:
| System temperatures | ΔT | Output vs catalogue value (approx.) |
|---|---|---|
| 75/65 °C | 50 | 100% |
| 70/55 °C | 42.5 | ≈80% |
| 55/45 °C (condensing boiler, heat pump) | 30 | ≈50% |
| 45/35 °C (heat pump) | 20 | ≈30% |
Corrections: when you need more
- Corner room (two external walls): about +10–20%.
- Large window or glazed wall: put the radiator under the window, 70–90% of its width, to stop the cold downdraught.
- Top floor or above a cold basement: +10–20%.
- High ceiling (over 3 m): proportionally more.
- Radiator in a niche or behind a decorative cover: output drops by 10–15%.
These corrections are guidance. A room-by-room heat loss calculation gives the exact result.
Panel radiators: what do types 11, 21, 22, 33 mean?
The first digit is the number of panels, the second the number of convector fin rows between them. Type 22 (two panels, two convectors) is the most common. For example, a type 22 panel 600 × 1000 mm gives about 1.8 kW at ΔT 50 — the exact value is in the manufacturer's table.
Most common mistakes
- Taking the output from the catalogue when the system runs at low temperature.
- One very long radiator in a room with two windows.
- Covering the radiator with curtains or a cover.
- An unbalanced system — even a correctly sized radiator stays cold if it does not get enough water.
Frequently asked questions
How many sections does an 18 m² room need?
An averagely insulated room needs ≈1.8 kW — about 10 sections of 180 W in a 75/65 °C system. At low temperature (55/45 °C) about 20, i.e. two radiators.
Aluminium or bimetal sections?
Similar in size and output. Bimetal sections withstand high pressure better and are less sensitive to water quality; aluminium is cheaper. For an individual system (1–2 bar) both are fine.
Can sections be added to an existing radiator?
On aluminium and bimetal sectional radiators, yes — with sections of the same model and new gaskets. The system has to be drained and then pressure-tested.
Sources
- EN 442 — output testing of radiators and convectors.
- EN 12831 — design heat load of buildings.